o not mount the instruments in or above the filling stream. Make sure

that you detect the product surface, not the inflowing product.

Fig. 7: Inflowing liquid

T

he socket piece should be dimensioned in such a way that the

antenna end protrudes at least 10 mm (0.4 in) out of the socket.

ca.

10 mm

Fig. 8: Recommended socket mounting

A

lign the sensor in liquids as vertical as possible to the product surface

to achieve optimum measurement.

Inflowing medium

Socket

Sensor orientation

16

VEGAPULS

66

enamel • 4 … 20 mA/HART two-wire