5 instrument repair – VEGA VEGAFLEX 67 (-40…+150°C) Foundation Fieldbus User Manual
Page 37
At "www.vega.com/downloads" go to "Software". Select under "plics
sensors and instruments", "Firmware updates" the respective instru-
ment series and software version. Load the zip file via the right mouse
key with "Save target as" e.g. on the desktop of your PC. Move with the
right mouse key to the folder and select "Extract all". Save the
extracted files, for example on the desktop.
Connect the signal conditioning instrument to power supply and
provide the connection from the PC to the instrument via the interface
adapter. Start PACTware and go via the menu "Project" to the VEGA
project assistant. Select "USB" and "Set instruments online". Activate
the project assistant with "Start". The assistant establishes the
connection automatically and opens the parameter adjustment window
"S
ensor # online parameter adjustment". Connect this parameter
adjustment window before you carry out further steps.
Select with the right mouse key the sensor in the project and go to
"A
dditional function". Then click to "Software update". The window
"S
ensor # software update" opens. PACTware checks now the sensor
data and displays the actual hardware and software version of the
sensor. This takes approximately 60 s.
Push the button "Update software" and select the previously extracted
hex file. Then the software update can be started. The additional files
are installed automatically. Depending on the sensor, this procedure
lasts up to 1 h. Then the message appears ""Software update
successfully executed".
8
.5 Instrument repair
If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our homepage at www.
vega.com under: "Downloads - Forms and certificates - Repair form".
By doing this you help us carry out the repair quickly and without
having to call back for needed information.
l
Print and fill out one form per instrument
l
Clean the instrument and pack it damage-proof
l
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
l
Please ask the agency serving you for the address of your return
shipment. You can find the respective agency on our website
www.vega.com under: "Company - VEGA worldwide"
On instruments with exchangeable rod, the rod must be unscrewed for
transport to avoid damages.
Return the parts separately for repair.
To loosen to rod, you require a fork spanner with wrench size 8.
1
Loosen the rod with a fork spanner (SW 8) applied to the flat
surfaces, provide counterforce with another fork spanner (SW 8)
Load sensor software to
PC
Prepare update
Load software into sen-
sor
Return of rod versions
VEGAFLEX
67 • Foundation Fieldbus
37
8 Maintenance and fault rectification
31856
-
EN
-120329