10 Supplement
VEGASON 61 • Profibus PA
28784-EN-130417
10 Supplement
10.1 Technical data
General data
Materials, wetted parts
Ʋ Process fitting, transducer
PVDF
Ʋ Seal between transducer and process
fitting
EPDM, FKM (Viton)
Materials, non-wetted parts
Ʋ Housing
Plastic PBT (polyester), Alu die-casting powder-coated,
316L
Ʋ Seal between housing and housing
cover
NBR (stainless steel housing), silicone (Alu/plastic hous-
ing)
Ʋ Inspection window in housing cover
Polycarbonate
Ʋ Ground terminal
316Ti/316L
Weight
1.8 … 4 kg (4 … 8.8 lbs), depending on the process
fitting and housing
Max. torque mounting boss
25 Nm
Output variable
Output signal
digital output signal, format according to IEEE-754
Cycle time
min. 1 s (dependent on the parameter setting)
Sensor address
126 (default setting)
Current value
10 mA, ±0.5 mA
Damping (63 % of the input variable)
0 … 999 s, adjustable
Met NAMUR recommendation
NE 43
Resolution, digital
> 1 mm (0.039 in)
Input variable
Measured variable
distance between lower edge of the transducer and
product surface
Measuring range
Ʋ Liquids
up to 5 m (16.4 ft)
Ʋ Bulk solids
up to 2 m (6.562 ft)
Dead band
0.25 m (0.82 ft)
Reference conditions to measuring accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Other reference conditions
Ʋ Reflector
ideal reflector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft)
Ʋ False reflections
Biggest false signal, 20 dB smaller than the useful signal