min. - min.detection or dry run detection) on the signal

conditioning instrument.
When used on a control system, the following values apply:

l

Mode min.

- Vibrating element uncovered - 16 mA ±1 mA

-

Vibrating element covered - 8 mA ±1 mA

l

Mode max.

- Vibrating element uncovered - 8 mA ±1 mA

-

Vibrating element covered - 16 mA ±1 mA

Control lamp for indication of the switching condition.

l

green = 8 mA

l

red = 16 mA

l

red (flashing) = Failure (<2.3 mA)

6.3 Function chart

Level switch VEGAVIB 65

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Mode on the

sensor

Level

Signal current -

Sensor

Signal lamp -

sensor

max.

Overfill protection

8 mA

Green

max.

Overfill protection

approx. 16 mA

red

min.

Dry run protection

approx. 8 mA

Green

min.

Dry run protection

approx. 16 mA

red

Signal lamp (5)

VEGAVIB 65 - with two-wire output

21

Set up

29286

-EN