5 setup – VEGA VEGABAR series 50_60 User Manual
Page 10
10
5 Setup
Electronics module • VEGABAR series 50/60
30175-EN-130322
5 Setup
5.1 Setup
After mounting a new electronics module and connecting to power
supply, the following data are loaded automatically from the meas. cell
electronics:
•
Instrument version
•
Serial number
•
Calibration date
•
Measuring range
•
Default
The instrument is generally ready for operation.
If you are using an electronics module without sensor serial number
or a "universal electronics module" from stock, you can load the
order-specific data into the sensor on site if required.
Information:
When loading on site, the file must first be downloaded from the Inter-
net (see "Load sensor data").
Go at www.vega.com to "Instrument search". The order data of the
sensor are displayed after entering the serial number.
Below the order data you will find "Sensor data for Service-DTM" as
XML file. Load this file with "Save as" on your PC and transfer it then
via PACTware and the Service DTM to the sensor.
As a rule, settings already carried out on site with the previous elec-
tronics module, such as min./max. adjustment etc., must be repeated.
Tip:
To do this, use the copy function of the display and adjustment mod-
ule or the adjustment software PACTware.
Setup
Load sensor data
Adjustment