6 Setup
VEGACAP 64 • - contactless electronic switch
30013-EN-130916
6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
On the electronics module you will find the following display and
adjustment elements:
•
Potentiometer for switching point adaptation
•
DIL switch for measuring range selection
•
DIL switch for mode adjustment - min./max.
•
Control lamp
Note:
As a rule, always set the mode with the mode switch (3) before start-
ing setup VEGACAP 64. The switching output will change if you set
the mode switch (3) afterwards. This could possibly trigger other con-
nected instruments or devices.
6.2 Adjustment elements
4
5
6
3
2
1
Fig. 10: Oscillator - Contactless electronic switch
1 Potentiometer for switching point adaptation
2 DIL switch for measuring range selection (with compensation button)
3 DIL switch for mode adjustment
4 Ground terminal
5 Connection terminals
6 Control lamp
The switching status of the electronics can be checked with closed
housing (only plastic housing), see "Function chart".
Note:
Screw the housing cover tightly up to the thread stop so that the
inspection glass is above the control lamp (LED).
To adjust VEGACAP 64, first of all remove the housing cover.
Function/Configuration