VEGA VEGASON 63 Profibus PA User Manual
Page 29
29
6 Set up with the display and adjustment module PLICSCOM
VEGASON 63 • Profibus PA
28786-EN-130417
reduced, false reflections by agitators or vessel installations can
cause measured value fluctuations. A false echo memory is thus
recommended.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:
•
Measured value presentation
•
Adjustment
•
Medium
•
Vessel form
•
Damping
•
Linearization curve
•
Sensor-TAG
•
Displayed value
•
Scaling unit (Out-Scale unit)
•
Positions after the decimal point (scaled)
•
Scaling PA/Out-Scale 4 values
•
Unit of measurement
•
Language
The following safety-relevant data are not read out or written:
•
Sensor address
•
PIN
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the follow-
ing menu items to the reset values (see chart):
2)
Menu section
Function
Reset value
Basic settings
Max. adjustment
0 m(d)
Min. adjustment
Meas. range end in
m(d)
3)
Medium
Liquid
Vessel form
not known
Damping
0 s
Linearization
Linear
Channel
PV lin. %
Sensor-TAG
Sensor
Display
Displayed value
PA-Out
Copy sensor data
Reset
2)
Sensor-specific basic adjustment.
3)
Depending on the sensor type, see chapter "Technical data".