beautypg.com

2 mounting instructions – VEGA VEGASON 63 Profibus PA User Manual

Page 11

background image

11

4 Mounting

VEGASON 63 • Profibus PA

28786-EN-130417

1

2

Fig. 3: Minimum distance to the max. level
1 Dead band

2 Reference plane

Information:

If the medium reaches the transducer, buildup can form on it and

cause faulty measurements later on.

1

3

2

100%

0%

Fig. 4: Measuring range (operating range) and max. measuring distance
1 full

2 empty (max. measuring distance)

3 Measuring range

Gauge pressure in the vessel does not influence VEGASON 63. Low

pressure or vacuum does, however, damp the ultrasonic pulses. This

influences the measuring result, particularly if the level is very low.

With pressures under -0.2 bar (-20 kPa) you should use a different

measuring principle, e.g. radar or guided microwave.

4.2 Mounting instructions

When mounting the VEGASON 63, keep a distance of at least

200 mm (7.874 in) to the vessel wall. If the sensor is installed in the

center of dished or round vessel tops, multiple echoes can arise.

These can, however, be suppressed by an appropriate adjustment

(see chapter "Setup").
If you cannot keep this distance you should carry out a false echo

storage before setup. This applies mainly if buildup on the vessel wall

Pressure/Vacuum

Installation position