2 principle of operation – VEGA VEGAVIB 63 - Relay (DPDT) User Manual
Page 8
With the serial number, you can access the delivery data of the
instrument via www.vega.com, "VEGA T
ools" and "serial number
search". In addition to the type label outside, you can also find the
serial number on the inside of the instrument.
3
.2 Principle of operation
VEGAVIB
63 is a point level sensor with vibrating rod for level
detection.
It is designed for industrial use in all areas of process technology and
is preferably used for bulk solids.
Typical applications are overfill and dry run protection. Thanks to its
simple and robust measuring system, VEGAVIB 63 is virtually
unaffected by the chemical and physical properties of the bulk solid.
It also works when subjected to strong external vibrations or changing
products.
Solid detection in water
If VEGAVIB 63 was ordered for solid detection in water, the vibrating
rod is calibrated to the density of water. If covered by water (density:
1 g/cm³/0.036 lbs/in) VEGAVIB 63 signals "uncovered". Only if the
vibrating element is also covered with solids (e.g. sand, sludge, gravel
etc.) will the sensor signal "covered".
Fault monitoring
The electronics module of VEGAVIB 63 monitors continuously the
following criteria:
l
Correct vibrating frequency
l
Line break to the piezo drive
If one of the stated malfunctions is detected or in case of power failure,
the electronics takes on a defined switching condition, i.e. the relay
deenergises (safe condition).
The vibrating rod is piezoelectrically energised and vibrates at its
mechanical resonance frequency of approx. 360 Hz. When the
vibrating rod is submerged in the product, the vibration amplitude
changes. This change is detected by the integrated electronics module
and converted into a switching command.
VEGAVIB
63 is a compact instrument, i.e. it can be operated without
external evaluation system. The integrated electronics evaluates the
level signal and outputs a switching signal. With this switching signal, a
connected device can be operated directly (e.g. a warning system, a
pump etc.).
The data for power supply are specified in chapter "Technical data".
Application area
Functional principle
Voltage supply
8
VEGAVIB
63 • - Relay (DPDT)
3 Product description
29277
-EN
-120418