4 … 20 mA signal missing
l
Wrong connection
à
Check connection according to chapter "Connection
procedure" and, if necessary, correct according to
chapter "Wiring plan"
l
No supply voltage
à
check cables for line break, repair, if necessary
l
supply voltage too low or load resistance too high
à
Check, adapt, if necessary
?
Current signal greater than 22 mA or less than 3.6 mA
l
Electronics defective
à
Exchange instrument or return instrument for repair
In Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
?
E013
l
no measured value available
à
sensor in boot phase
à
sensor does not find an echo, e.g. because of faulty
installation or incorrect parameter adjustment
?
E017
l
Adjustment span too small
à
Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E036
l
no operable sensor software
à
Carry out software update or send instrument for repair
?
E041
l
Hardware error, electronics defective
à
Exchange instrument or return instrument for repair
Fault messages via the indi-
cating/adjustment module
Maintenance and fault rectification
VEGASON 66 - 4 ... 20 mA/HART - four-wire