n the main menu item "Basic adjustment", the individual submenu
items should be selected one after the other and provided with the
correct parameter values.
S
tart your parameter adjustment with the following menu items of the
basic adjustment:
P
roceed as follows:
1
M
ove from the measured value display to the main menu by
pushing [OK].
▶
B
asic adjustment
D
isplay
D
iagnostics
S
ervice
I
nfo
2
S
elect the menu item "Basic adjustment" with [->] and confirm with
[OK]
. N
ow the menu item "Min. adjustment" is displayed.
M
in. adjustment
0.00 %
=
5.000 m(d)
4.000
m(d)
3
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4
E
nter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5
S
ave the settings with [OK] and move to "Max. adjustment" with [-
>
]
.
P
roceed as follows:
M
ax. adjustment
100.00 %
=
1.000 m(d)
2.000
m(d)
1
P
repare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2
E
nter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
Carrying out min. ad-
justment
Carrying out max. ad-
justment
VEGAPULS
62
standpipe version • 4 … 20 mA/HART four-wire