With the potentiometer you can adapt the switching point to the

solid. It is already preset and must only be modified in special

cases.
By default, the potentiometer of VEGAVIB 66 is set to

complete right position (>0.02 g/cm³ or >0.0008 lbs/in³). In

case of very light-weight solids, you have to turn the

potentiometer to the complete left position (>0.008 g/cm³ or

>0.0003 lbs/in³). Hence the VEGAVIB 66 will be more

sensitive and can detect light-weight solids more reliably.
For instruments detecting solids in water, these values are not

applicable. The potentiometer is preset and must not be

changed.

With the mode adjustment (min./max.) you can change the

switching condition of the transistor output. You can set the

required mode according to the "Function chart" (max. - max.

detection or overfill protection, min. - min. detection or dry run

protection).
We recommend connecting according to the quiescent current

principle (transistor blocks when the switching point is

reached) because the transistor output takes on the same

(safe) condition if a failure is detected.

Control lamp for indication of the switching condition.

l

green = output conducts

l

red = output blocks

l

red (flashing) = failure

6.3 Function chart

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Level

Switching sta-

tus

Control lamp

Mode max.

Overfill protection

transistor con-

ducts

Green

Mode max.

Overfill protection

transistor blocks

red

Switching point adaptation (1)

Mode adjustment (2)

Signal lamp (5)

22

VEGAVIB 66 - with transistor output