beautypg.com

VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) standpipe ver. Foundation Fieldbus User Manual

Page 45

background image

Measuring range

up to 5.85 m (19.19 ft)

5)

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+18

… +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

-

Reflector

ideal reflector, e.g. metal plate 2 x 2 m

-

False reflections

Biggest false echo, 20 dB smaller than the useful
echo

Characteristics and performance data

Frequency

C-band (6 GHz technology)

Step response or adjustment time

6)

> 1

s (dependent on the parameter setting)

Max. level change

adjustable up to 1 m/min. (dependent on the
parameter adjustment)

Max. emitted HF power of the antenna system

-

Pulse peak power approx.

0.1 mW

-

Pulse duration

< 2

ns

-

SAR value

7)

0.471 mW/kg

Measuring accuracy

Resolution, general

max. 1 mm (0.039 in)

Deviation

8)

see diagrams

5)

According to the respective standpipe length.

6)

Time to output the correct level (with max. 10 % deviation) after a sudden
level change.

7)

at the aperture of a horn antenna with ø 150 mm

8)

Incl. non-linearity, hysteresis and non-repeatability.

VEGAPULS

66 standpipe version • Foundation Fieldbus

45

10 Supplement

28744

-EN

-090305