VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) standpipe ver. Foundation Fieldbus User Manual
Page 45
Measuring range
up to 5.85 m (19.19 ft)
5)
Reference conditions to measuring accuracy (similar to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
-
Temperature
+18
… +30 °C (+64 … +86 °F)
-
Relative humidity
45 … 75 %
-
Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Other reference conditions
-
Reflector
ideal reflector, e.g. metal plate 2 x 2 m
-
False reflections
Biggest false echo, 20 dB smaller than the useful
echo
Characteristics and performance data
Frequency
C-band (6 GHz technology)
Step response or adjustment time
6)
> 1
s (dependent on the parameter setting)
Max. level change
adjustable up to 1 m/min. (dependent on the
parameter adjustment)
Max. emitted HF power of the antenna system
-
Pulse peak power approx.
0.1 mW
-
Pulse duration
< 2
ns
-
SAR value
7)
0.471 mW/kg
Measuring accuracy
Resolution, general
max. 1 mm (0.039 in)
Deviation
8)
see diagrams
5)
According to the respective standpipe length.
6)
Time to output the correct level (with max. 10 % deviation) after a sudden
level change.
7)
at the aperture of a horn antenna with ø 150 mm
8)
Incl. non-linearity, hysteresis and non-repeatability.
VEGAPULS
66 standpipe version • Foundation Fieldbus
45
10 Supplement
28744
-EN
-090305