VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) standpipe ver. Foundation Fieldbus User Manual
Page 30
3
Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5
Save the settings with [OK] and move to "Max. adjustment" with [-
>
]
.
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1
Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3
Save the settings with [OK] and move to "Medium selection" with
[->]
.
Each product has different reflective properties.
According to the conductivity and the dielectric value of liquids, the
reflection properties can differ considerably. Therefore additional
options such as "Solvent", "Chem. mixture" and "Water based" are
offered below the menu item Liquid.
Through this additional selection, the sensor is adapted perfectly to the
product and measurement reliability, particularly in products with bad
reflective properties, is considerably increased.
Medium
Liquid
Water based
Acids/Bases
Enter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
Carrying out max. ad-
justment
Medium selection
30
VEGAPULS
66 standpipe version • Foundation Fieldbus
6 Set up with the indicating and adjustment module PLICSCOM
28744
-EN