10.1 Technical data

General data
Materials, wetted parts

Ʋ Process fitting, transducer

PVDF

Ʋ Seal transducer/process fitting

EPDM, FKM (Viton)

Materials, non-wetted parts

Ʋ Housing

Plastic PBT (polyester), Alu die-casting powder-coated,

316L

Ʋ Seal between housing and housing

cover

NBR (stainless steel housing), silicone (Alu/plastic hous-

ing)

Ʋ Inspection window in housing cover

Polycarbonate

Ʋ Ground terminal

316Ti/316L

Weight

1.8 … 4 kg (4 … 8.8 lbs), depending on the process

fitting and housing

Max. torque mounting boss

25 Nm

Output variable
Output signal

4 … 20 mA/HART (active)

HART output values

Ʋ HART value (Primary Value)

Distance to the level

Ʋ HART value (Secondary Value)

Temperature

Ʋ HART value (3rd Value)

Distance to the level - scaled

Resolution

1.6 µA

Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Current limitation

22 mA

Load

< 500 Ω

4)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Met NAMUR recommendation

NE 43

Input variable
Measured variable

distance between lower edge of the transducer and

product surface

Measuring range

Ʋ Liquids

up to 8 m (26.25 ft)

Ʋ Bulk solids

up to 3.5 m (11.48 ft)

Dead band

0.4 m (1.312 ft)

Reference conditions to measuring accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

4)