beautypg.com

VEGA VEGASON 62 4 … 20 mA_HART - four-wire User Manual

Page 27

background image

27

6 Set up with the display and adjustment module PLICSCOM

VEGASON 62 • 4 … 20 mA/HART - four-wire

28779-EN-130417

Linear

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

In this menu item you can enter an unambiguous designation for the

sensor, e.g. the measurement loop name or the tank or product des-

ignation. In digital systems and in the documentation of larger plants,

a singular designation should be entered for exact identification of

individual measuring points.

Sensor-TAG

Sensor

With this menu item, the Basic adjustment is finished and you can

now jump to the main menu with the [ESC] key.

High sockets or vessel installations, such as e. g. struts or agitators as

well as buildup and weld joints on the vessel walls, cause interfering

reflections which can impair the measurement. A false echo storage

detects and marks these false echoes, so that they are no longer

taken into account for the level measurement. A false echo memory

should be created with low level so that all potential interfering reflec-

tions can be detected.

False signal suppression

Change now?

Proceed as follows:
1. Move from the measured value display to the main menu by

pushing [OK].

2. Select the menu item "Service" with [->] and confirm with [OK].

Now the menu item "False signal suppression" is displayed.

3. Confirm "False signal suppression - Change now" with [OK] and

select in the below menu "Create new". Enter the actual distance

from the sensor to the product surface. All false signals in this

area are detected by the sensor and saved after confirming with

[OK].

Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.

The menu item "Extended setting" offers the possibility to optimise

VEGASON 62 for applications in which the level changes very quickly.

To do this, select the function "Quick level change > 1 m/min.".

Sensor-TAG

False signal suppression

Extended setting/Quick

level change