7 Maintenance and fault rectification

7.1 Maintenance

When used as directed in normal operation, VEGAVIB 67 is

completely maintenance-free.

7.2 Fault rectification

VEGAVIB 67 offers maximum reliability. Nevertheless faults

can occur during operation. These may be caused by the

following, e.g.:

l

Sensor

l

Process

l

Power supply

l

Signal processing

The first measure to be taken is checking the output signal. In

many cases, the causes can such be determined and failures

can be rectified.

If the following measures are not successful, please call in

urgent cases the VEGA service hotline at +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock.

Since we offer this service world-wide, the support is only

available in the English language. The service is free of

charge, only the standard telephone costs will be charged.

?

VEGAVIB 67 signals "covered" when the vibrating element

is not submerged (overfill protection)

?

VEGAVIB 67 signals "uncovered" when the vibrating

element is submerged (dry run protection)

l

Supply voltage too low

à

Check the power supply

l

Electronics defective

à

Press the mode switch (min./max.). If the instrument

then changes the mode, the instrument may be

mechanically damaged. Should the switching function

in the correct mode still be faulty, return the instrument

for repair.

à

Push the mode switch. If the instrument then does not

change the mode, the oscillator may be defective.

Exchange the oscillator.

Fault rectification

24 hour service hotline

Checking the switching signal

VEGAVIB 67 - with two-wire output

27

Maintenance and fault rectification