5 how to proceed in case of repair – VEGA VEGACAP 65 - transistor (NPN_PNP) User Manual
Page 28
28
7 Maintenance and fault rectification
VEGACAP 65 • - transistor (NPN/PNP)
30018-EN-130916
5. Shift the gravity weight again flush to the cable and fix it with the
two pins.
6. Mount the probe into the vessel. Make sure that the probe is
uncovered.
2
1
Fig. 30: Compensation key
1 Measuring range selection switch (compensation key)
2 Control lamp
7. Keep the measuring range selection switch (1) pushed until the
control lamp (2) flashes green.
8. Hence the probe is compensated to the modified length.
9. Carry out the adjustment again. See chapter "Set-up, adjustment
elements".
7.5 How to proceed in case of repair
You can find a repair form as well as detailed information on how to
pr
cates".
By doing this you help us carry out the repair quickly and without hav-
ing to call back for needed information.
If a repair is necessary, please proceed as follows:
•
Print and fill out one form per instrument
•
Clean the instrument and pack it damage-proof
•
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
•
Please contact for the return shipment the agency serving you. You
can find the agency on our home page