4 Mounting

VEGACAP 65 • - transistor (NPN/PNP)

30018-EN-130916

If condensate forms on the vessel top, the run-off liquid can cause

bridging and hence faulty switchings.
For this reason, use a screening tube or a longer insulation. The

length depends on the amount of condensate and the drain-off be-

haviour of the product.

4.2 Mounting instructions

Due to the effects of agitators, equipment vibration or similar, the level

switch can be subjected to strong lateral forces. For this reason, do

not use an overly long electrode for VEGACAP 65, but check if you

can mount a short level switch on the side of the vessel in horizontal

position.

If the instrument is mounted in the filling stream, unwanted false

measurement signals can be generated. For this reason, mount the

instrument at a position in the vessel where no disturbances, e.g. from

filling openings, agitators, etc., can occur.
This applies particularly to instrument versions with a longer probe.

Fig. 5: Inflowing medium

The probe should protrude into the vessel to avoid buildup. For that

reason, avoid using mounting bosses for flanges and screwed fittings.

This applies particularly to use with adhesive products.

In silos with bulk solids, material cones can form which change the

switching point. Please keep this in mind when installing the sensor

in the vessel. We recommend selecting an installation location where

the probe detects the average value of the material cone.
The probe must be mounted in a way that takes the arrangement of

the filling and emptying apertures into account.

Condensation

Agitators and fluidization

Inflowing medium

Socket

Material cone