Fig. 7: Indicating elements of VEGADIS 11
1

Bar graph

2

Tendency indication

3

Digital value

l

four positions as well as signa and decimal point

l

individual scaling between -9999 … +9999

The display outputs the current 4 … 20 mA as bar graph and
digital value.

With 4 mA no segment of the bar graph appears, with 20 mA
all segments appear. This assignment is fix.

You can scale the digital value to any value between -9999 …
+

9999 via the adjustment module.

To scale the indication, proceed as follows:

1

Initial value: Set rotary switch to "zero"

2

Set the requested value, e.g. 0 with the [+] and [-] keys

3

Final value: Set the rotary switch to "span"

4

Set the requested value, e.g. 1000 with the [+] and [-] keys

5

Decimal point: Set the rotary switch to "point"

6

With the [+] and [-] keys you can adjust the requested
value, e.g. 8888 (no decimal point)

7

Set rotary switch to "OPERATE"

8

Screw the housing cover on

The adjustment data are effective, the output current 4 … 20 mA
corresponds to the actual level.