9 supplement, 1 technical data, 9supplement – VEGA VEGATOR 631 Ex User Manual
Page 29
9
Supplement
9
.1 Technical data
General data
Series
Module unit with plug-in socket for mounting on
carrier rail 35 x 7.5 or 35 x 5 according to EN 50022
Weight
170 g (6 oz)
Housing material
Noryl SE100, Lexan 920A
Socket material
Noryl SE100, Noryl SE1 GFN3
Power supply
Operating voltage
20 … 253 V AC, 50/60 Hz, 20 … 72 V DC
Max. power consumption
1.5 W (1 … 9 VA)
Fuse
-
Supply area
T
315 mA, 253 V
-
Switching off possibility
min. 35 A at 253 V AC or 125 V DC
Sensor input
Quantity
1 x level detection or 1 x pump control (min./max.)
Response resistor
1 … 200 kΩ adjustable
Parallel resistor for fault monitoring
220 kΩ
Measuring circuit
max. 5 V eff., max. 1 mA
Permissible line capacitance
1 x 100 nF or 2 x 70 nF with min./max. control
Switching hysteresis
15 %
Adjustment elements
DIL switch block
for preadjustment of the integration time and mode
Potentiometer
for switching point adjustment
Control lamps in the front plate
-
Status indication operating voltage
Signal lamp green (LED)
-
Status indication fault signal
Signal lamp red (LED)
-
Status indication switching point control
Signal lamp yellow (LED)
Relay output
Quantity
1
Mode
A/B switch (A - max. detection or overfill protection,
B - min. detection or dry run protection)
Integration time
500 ms
Contact
1 spdt for each output
Contact material
AgNi, hard gold-plated
VEGATOR
631 Ex • Signal conditioning instrument
29
9 Supplement
23440
-EN
-090130