beautypg.com

9 supplement, 1 technical data, 9supplement – VEGA VEGATOR 631 Ex User Manual

Page 29

background image

9

Supplement

9

.1 Technical data

General data

Series

Module unit with plug-in socket for mounting on
carrier rail 35 x 7.5 or 35 x 5 according to EN 50022

Weight

170 g (6 oz)

Housing material

Noryl SE100, Lexan 920A

Socket material

Noryl SE100, Noryl SE1 GFN3

Power supply

Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 72 V DC

Max. power consumption

1.5 W (1 … 9 VA)

Fuse

-

Supply area

T

315 mA, 253 V

-

Switching off possibility

min. 35 A at 253 V AC or 125 V DC

Sensor input

Quantity

1 x level detection or 1 x pump control (min./max.)

Response resistor

1 … 200 kΩ adjustable

Parallel resistor for fault monitoring

220 kΩ

Measuring circuit

max. 5 V eff., max. 1 mA

Permissible line capacitance

1 x 100 nF or 2 x 70 nF with min./max. control

Switching hysteresis

15 %

Adjustment elements

DIL switch block

for preadjustment of the integration time and mode

Potentiometer

for switching point adjustment

Control lamps in the front plate

-

Status indication operating voltage

Signal lamp green (LED)

-

Status indication fault signal

Signal lamp red (LED)

-

Status indication switching point control

Signal lamp yellow (LED)

Relay output

Quantity

1

Mode

A/B switch (A - max. detection or overfill protection,
B - min. detection or dry run protection)

Integration time

500 ms

Contact

1 spdt for each output

Contact material

AgNi, hard gold-plated

VEGATOR

631 Ex • Signal conditioning instrument

29

9 Supplement

23440

-EN

-090130