VEGA VEGATOR 536 Ex User Manual
Page 4
4
VEGATOR 536 Ex
Inputs
Number
1 sensor input
Data transmission
analogue
Switching threshold
12 mA
Current limitation
24 mA (permanently shortcircuit proof)
Sensor supply voltage
15 … 18 V DC
Connection line
2-wire
Resistance per conductor
max. 35
Ω
Integration time
0,2 … 20 s
(adjustment via DIL-switch)
Relay output
Number, function
1 switching relay (spdt), 1 fail safe relay
Mode
A/B-switch
A - max. detection or overfill protection
B - min. detection or dry run protection
Contact
1 spdt each
Contact material
AgCdO and Au plated
Turn-on voltage
min. 10 mV
max. 250 V AC, 250 V DC
Switching current
min. 10 µA
max. 3 A AC, 1 A DC
Breaking capacity
max. 500 VA AC, 54 W DC
Transistor output
Number, function
2, synchronously switching with the relays
Galvanic isolation
floating
Max. values
U
B
max. 36 V DC
I
B
max. 60 mA
Transistor voltage loss
U
CE
min. - 1,5 V at I
B
60 mA
Blocking current
< 10 µA
Indicating elements
LED in the front plate
- green on
operating voltage on
- yellow
switch point control
- red
fault signal
Explosion protection
Certificate
conformity certificate
TÜV 01 ATEX 1781
Classification
ATEX II GD EEx ia IIC/IIB
Please note the attached safety instructions containing important information on installation and
operation in Ex areas.
These safety instructions are part of the operating instructions manual and come with the Ex
approved instruments.
Product description