Channel Numbers

-

Channel 1

Primary value

-

Channel 2

Secondary value 1

-

Channel 3

Secondary value 2

-

Channel 4

Temperature value

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Dynamic behaviour output

Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 28: Sudden change of the process variable, dead time t

T

, rise time t

A

and step response time t

S

1

Process variable

2

Output signal

Dead time

≤ 150 ms

Rise time

≤ 100 ms (10 … 90 %)

Step response time

≤ 250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Input variable

Adjustment

Adjustment range of the min./max. adjustment relating to the nominal measuring range:

-

percentage value

-10 … 110 %

-

pressure value

-20 … 120 %

Adjustment range of the zero/span adjustment relating to the nominal measuring range:

-

zero

-20 … +95 %

VEGABAR

65 • Foundation Fieldbus

53

10 Supplement