Pressure transmitter D91 (Profibus PA)

23

Setup

ti

1

s

Adjustment without taking the current
pressure into account (dry adjustment)

Adjustment without pressure comprises four
steps:
1 Selection of the unit in which the adjustment

is to be carried out

2 Offset correction
3 Adjustment of zero
4 Adjustment of span

The offset correction (only in gauge pressure
mode) defines the reference positions for the
measurement. It can be carried out:
- before or after adjustment of zero and

span

- before or after installation of transmitters.

The transmitter must be unpressurised for
the offset correction!

Adjustment without pressure can be carried
out with the instrument mounted or dis-
mounted (e.g. workroom). Any ambient pres-
sure has no effect on the adjustment.

1 Selection of the unit

Choose the unit with the "+" or "–"
key. Save the selected unit with
the "OK" key.

2 Adjustment of zero

Adjust zero with the "+" or "–" key
and save with the "OK" key.

Zero

0,0

mbar

Span

100,0

mbar

4 Adjustment of span

Adjust span with the "+" or "–" key
and save with the "OK" key.

Note:

- A modification of zero does not influence

the span.

- By pushing the "+" and "–" keys, the output

remains on the last value - only after saving
with the "OK" key will the output take on the
adjusted value.

Evaluation

Linearisation curve

Is only displayed if a linearisation
curve has been activated with VVO.

Adjustment of the integration time

An integration time t

i

of 0 s … 50 s

can be adjusted with the "+" or "–"
key for damping of pressure

shocks. The adjusted value can be saved
with the "OK" key.

Selection of the indicated unit

The measurement unit for the meas-
ured value display as well as for
the display module can be selected
here (with the "+" or "–" key and the
"OK" key). If you select "scal.", the
scaled PA output value will be dis-
played (as adjusted under "Scaling
outp.").

Adjust

without

pres.

Unit

0,0

mbar

psi
kPa
inHg

Lin.-

curve

activ

Unit

0,0

skal

psi
kPa
%
m
ft
inch
mbar