beautypg.com

VEGA VEGAPULS 41 Profibus PA User Manual

Page 46

background image

46

VEGAPULS 41 – Profibus PA

27292-EN-041227

Technical data

Measured value display (optional)

Liquid crystal display

- in the sensor

scalable measured value output as a graph and
as a number

- external, powered by the sensor

scalable measured value output as a graph and

as a number. Measured value display can be
mounted up to 25 m away from the sensor (max.
cable length 25 m).

Adjustment

- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- SIMATIC-PDM
- PACTware

TM

Accuracy

1)

(typical values under reference conditions, all statements relate to the nominal range)

Characteristics

linear

Accuracy

see diagram

Resolution in general

max. 1 mm

Resolution of the output signal

1 mm or 0.005 %

Ambient conditions

Ambient temperature on the housing

-40°C … +80°C

Process temperature (flange temp.)

-40°C … +130°C

Storage and transport temperature

-60°C … +80°C

Vessel pressure

-1 … 3 bar (-100 … 300 kPa)

Protection

IP 66 and IP 67

Protection class

- two-wire sensor

II

- four-wire sensor

I

Overvoltage category

III

0,5 m

10 m

10 mm

5 mm

-5 mm

-10 mm