3 electrical connection, 1 connection - connection cable - screening, 1 connection – connection cable – screening – VEGA VEGAPULS 41 Profibus PA User Manual
Page 26
26
VEGAPULS 41 – Profibus PA
27292-EN-041227
Electrical connection
3 Electrical connection
3.1 Connection – Connection cable
– Screening
Safety information – Qualified person-
nel
Instruments which are not operated with
protective low voltage or DC voltage must
only be connected by qualified personnel.
This also applies to the configuration of
measuring systems planned for Ex environ-
ment.
As a rule, do all connecting work in the com-
plete absence of line voltage. Always switch
off the power supply before you carry out
connecting work on the radar sensors. Pro-
tect yourself and the instruments.
Connection cables and bus configura-
tion
Note the Profibus specification. The connec-
tion cables must be specified for the ex-
pected operating temperatures in your
systems and must have an outer diameter of
6 … 12 mm, to ensure the seal effect of the
cable entry on the sensor.
For power supply and bus communication, a
two-wire cable acc. to the Profibus specifica-
tion (up to max. 2.5 mm
2
cross-section area
of conductor) is used. The electrical connec-
tion on the sensor is made by spring-loaded
terminals.
In a laboratory set-up, a Profibus system will
also work with standard, unshielded two-wire
cable. In practice, however, an automation
network and bus system can only be pro-
tected reliably against electromagnetic inter-
ference by using screened cable. Acc. to the
Profibus specification (IEC 1158-2),
screened and twisted cables are prescribed.
All participants are connected in one line
(serially). At the beginning and end points of
a segment, the bus is terminated by an ac-
tive bus termination. On the DP bus level,
most participants already have a bus termi-
nation implemented. With more than 32 par-
ticipants on the DP level, a so-called repeater
must be used to open and combine another
DP level with a max. of 32 additional partici-
pants. On the PA bus branch of the segment
coupler, the PA radar sensors also work with
a max. of 32 participants (Ex max. 10 partici-
pants).
A PA sensor can work only in conjunction with
a Profibus DP system, to which a Profibus PA
subsystem is connected. A PA Profibus par-
ticipant must consume at least 10 mA of sup-
ply current.
Connection cable and cable length
Connection cables must correspond to the
Profibus specification and the FISCO model.
The sensor cable must be in conformity with
the values of the reference cable acc. to
IEC 61158-2:
0.8 mm
2
; R
DCmax.
= 44
Ω/km;
Z
31.25kHz
= 80 … 120
Ω; damping = 3 dB/km;
C
asymmetric
= 2 nF/km.
The max. cable length first of all depends on
the transmission speed:
up to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Profibus P
ofibus P
ofibus P
ofibus P
ofibus PA
A
A
A
A
up to 94 kbit/s: 1200 m Profibus DP
up to 188 kbit/s: 1000 m Profibus DP
up to 500 kbit/s: 500 m Profibus DP
up to 1500 kbit/s: 200 m Profibus DP
up to 12000 kbit/s: 100 m Profibus DP