ake sure that all parts of the instrument in contact with the measured

product, especially the sensor element, process seal and process

tting, are suitable for the existing process conditions such as process

pressure, process temperature as well as the chemical properties of
the medium.

Y

ou can find the specifications in chapter "Technical data" in the or on

the type label.

4.2 Mounting instructions

W

hen mounting VEGAPULS 66, keep a distance of at least 500 mm

(19.69

in) to the vessel wall. If the sensor is installed in the center of

dished or round vessel tops, multiple echoes can arise. These can,
however, be suppressed by an appropriate adjustment (see chapter
"

Setup").

I

f you cannot keep this distance you should carry out a false echo

storage before setup. This applies mainly if buildup on the vessel wall
is expected. In this case, we recommend repeating a false echo
storage later with existing buildup.