VEGASON 83 … 87
23
3 Environment
3
Environment
3.1
Installation recommendations
relating to liquid tank / vessels
Installation under normal conditions
Flange version
Mounting on a very short, generally on a DIN-socket piece
available on the tank.
The max. filling of the tank depends on the min. distance
of the respective sensor or compact instrument.
Installation under special conditions
If the min. distance of the sensor is decreased, mounting
on a socket piece is necessary.
Generally the diameter of the socket piece should be as
large as possible and the socket length should be as short
as possible.
Min. distance
Separate version
Mounting of the transducer in a very small hole (ø 35 mm)
in the tank ceiling. The mounting procedure can be
provided via an available access hatch.
The max. filling of the tank depends on the min. distance
of the respective sensor or compact instrument.
Min. distance
ø socket piece
Length of socket piece
ø
L
Tube length L to tube diameter ø
VEGASON
83
84
85
87
Socket piece-ø
100
400
–––
–––
–––
150
400
300
300
–––
200
500
400
400
–––
250
600
500
500
–––
300
–––
600
600
–––
350
–––
700
700
350
See the following schedule as general tube relating to the
dimensioning of the socket piece length to socket piece
diameter.
~45
°
Min. distance