6
VEGATRENN 548 V Ex
Product description
Electrical connection
Multiple plug component
acc. to DIN 41 612, series F, 33-pole,
3 rows d, b, z (partly equipped)
In conjunction with
- carrier
BGT 596 Ex, BGT LOG 571
connection to appropriate Ex-module
- housing type 506
connection to screw terminals (max. 2,5 mm
2
)
Protective measures
Protection
- not mounted
IP 00
- mounted in BGT 596 Ex oder
BGT LOG 571
front side (completely equipped): IP 40
upper and lower side: IP 20
wiring side: IP 00
- mounted in housing type 506
front side (completely equipped): IP 40
housing gerneal: IP 30
terminal side: IP 20
Protection class (in housing type 506)
II
Overvoltage category
II
Electrical separating measures
Galvanic isolation
between intrinsically safe circuits and
not intrinsically safe circuits as well as
against the power supply
- reference voltage
250 V
- isolation resistance
1,5 kV
Common potential
with the intrinsically safe circuits
CE-conformity
The Ex-separator VEGATRENN 548 V Ex meets the portective regulations of EMVG
(89/336/EWG) and NSR (73/23/EWG). The conformity has been judged acc. to the following
standards:
EMVG
Emission
EN 50 081
Susceptibility
EN 50 082
NSR
EN 61 010
Mechanical data
Series
module unit for 19“-carrier or housing type 506
Dimensions
W = 25,4 mm (5 TE), H = 128,4 mm, D = 162 mm
Weight
approx. 350 g
Ambient conditions
Permissible ambient temperature
-20°C … +60°C
Storage and transport temperature
-40°C … +80°C