VEGATRENN 548 V Ex
5
Product description
1.2 Technical data
Power supply
Operating voltage
U
nenn
= 24 V AC (20 … 53 V), 50/60 Hz
= 24 V DC (20 … 72 V)
Power consumption
approx. 4 W, approx. 6 VA
Fuse
1 A, slow-blow
Signal conditioning instrument circuit
For connection to
signal conditioning instrument VEGAMET 514 V,
515 V or EV-card of VEGALOG 571
Input voltage
U
nenn
= 25 V DC with VEGAMET
= 24 V DC with EV-card VEGALOG
The signal conditioning instrument circuit must only be connected to instruments with an
operating votlage less than 250 V.
Sensor circuit
Number
3 branches with 5 sensor current circuits each
Sensors
hydrostatic pressure transmitter with
electronics type B (VBUS)
Voltage
at 5 mA approx. 15 V DC, at 25 mA approx.
13,5 V DC
Current limitation
at approx. 30 mA, shortcircuit proof
Fuse
per circuit 1 fuse 40 mA, slow-blow
Connection line
2-wire (standard line) *
)
Resistance per conductor
max. 15
Ω
Line length
max. 1000 m
Sensor circuits, Ex-technical data
Classification
[EEx ia] IIC, [EEx ia] IIB, [EEx ib] IIC, [EEx ib] IIB
Max. values (per branch)
- voltage
U
O
- 18,2 V
- current
I
O
- 270 mA
- efficiency
P
O
- 926 mW
Characteristics
linear
EEx ia IIC
EEx ia IIB
EEx ib IIC
EEx ib IIB
Max. permissible outer inductance L
a
0,41 mH
1,8 mH
0,41 mH
1,8 mH
Max. permissible outer capacitance C
a
83 nF
384 nF
290 nF
1300 nF
The intrinsically safe sensor current circuits are reliably galvanically isolated from the not
intrinsically safe circuits up to a peak value of the nominal voltage of 375 V.
Indicating elements
LED in front plate
green on: operating voltage on
*
)
screened cable is recommended for electromagnetic interferences.