Pressure transmitter D85

27

Setup

The most important adjustment steps

On the following four pages you see a menu
schematic of the HART

®

handheld in conjunc-

tion with pressure transmitters D80 … D87.
The most important adjustment steps are
marked in the menu schematic with the letters
A … D. If you are not familiar with HART

®

handheld, please note:

After entering a parameter, first push the
"

ENTER" key. The adjustment is saved in the

handheld, but not in the sensor itself.

After you have pushed "

ENTER", you have to

push "

SEND" (here in the example for the

min. adjustment), to transfer the input to the
sensor.

After pushing "

SEND", a warning is displayed

that you are about to change device output
and for safety reasons, you should switch
your system to manual operation. Push "

OK"

and the adjustment is now transferred to the
sensor.

After a moment, you are asked to switch the
system from manual to automatic operation.
Confirm with "

OK"

and then with "

HOME".

You are now in the initial menu.

Generic: SENSOR
PV LVR

0.000 mbar

10.000

mbar

HELP DEL

ESC ENTER

Generic: SENSOR

1 PV

LRV

2 PV

URV

HELP SEND

HOME

4.1

(5.1)

Empty adjustment without
medium

Generic: SENSOR

– WARNING –

Pressing „OK“ will
change device output

Put loop in manual

ABORT OK

Generic: SENSOR
Online (general)

1 Sensor unit
2 PV

80.945 mbar

3 PV Analog output
4 PV LRV
5 PV URV

HELP

SAVE

Generic: SENSOR

1 PV

LRV

2 PV

URV

HELP

HOME

Generic: SENSOR

– WARNING –

Return control loop to
automatic control

OK