Manual override

The manual override is applied by rotating

the 8 mm Allen key (not supplied) to the

required position. Observe the direction of

rotation symbol.

Function test

The indicator light shows whether the

positioner is in operation or not. Moreover,

the indicator shows the control status and

faults.
Constant light

- normal operation

No light

- no operation or no power supply

Intermittent light (1 Hz)

- self adjusting-mode

Intermittent light (3 Hz):

- power supply too low

- insufficient valve stroke (<20 s)

- end-position cannot be reached.