Danfoss AMV 413 User Manual
Page 5

55
Installation Guide
AMV 410, AMV 413
Danfoss Heating
VI.AA.U4.7S
DEN-SMT/SI
ENGLISH
Safety Notes
Prior to assembly and commissioning 
to avoid injury of persons and damages 
of the devices, it is absolutely necessary 
to carefully read and observe these 
instructions.
Necessary assembly, start-up, and 
maintenance work must be performed 
only by qualified, trained and authorized 
personnel. 
Prior to assembly and maintenance work 
on the controller, the system must be:
- depressurized, 
- cooled down,
- emptied and 
- cleaned.
Please comply with the instructions of the
system manufacturer or system operator.
Definition of Application
The electrical actuator is used in 
connection with the following valves: 
VFG 2(21), VFG 25, VFU 2, VFGS 2, AFQM 
and AFQM 6.
Fields of application are the temperature 
control of water, water-glycol mixtures 
and steam for heating, district heating and 
cooling systems.
Safety Return Function and 
Effective Direction 
2
Safety function and effective direction of 
stem: valid only for AMV 413.
Mounting
Permissible Installation Positions
1
Valve Installation
3
1. Install strainer in front of valve.
2. Rinse system before installing valve. 
3. Observe flow direction 
on the valve
body.
Flanges
in the pipeline system must be
in parallel direction, the sealing surfaces
must be clean and undamaged.
4. Install valve.
Actuator and Valve Installation
4
The actuator must only be mounted with 
the stem retracted 
.
Stroke indicator
must be in position
.
On delivery the stem is retracted with a 
screwed-in mounting screw 
.
If this is not the case, then:
1. Carry out the electrical connection, see 
next section.
2. Press push-button
and completely
retract the stem
.
3. Screw in mounting screw
up to its
stop.
4. Place actuator on the valve and align.
5. Tighten union nut 
torque 100 Nm.
6.
It is absolutely necessary to unscrew 
the mounting screw 
, otherwise, the
actuator is out of function.
7. If the actuator is installed in a downward
hanging position
, remove label
.
Insulation
5
Dimensions
6
Flanges: connection dimensions acc. to 
EN 1092-2, seal form C.
Electrical Connection
7
HIGH VOLTAGE !
Danger of injury and life in case of
improper handling.
Switch off power supply prior to 
connecting lines. 
The electrical connection must only be 
performed by an expert electrician.
Procedure
1. Unscrew cap nut 
and remove cover
.
2. Connect lines in accordance with
connection diagram.
3. Prior to remounting the cover, carry out
settings at the actuator, see part
8
.
Electrical Connection Diagram
8
Connection for:
STB - Safety Temperature Limiter 
STW - Safety Temperature Monitor
SDB - Safety Pressure Limiter
Prior to connection, it is absolutely necessary
to remove the jumper (terminals 4-7).
Only types AMV 413 with safety return
function.
Mechanical Stroke Setting
9
The stroke of the electrical actuator must 
be adjusted to the valve stroke.
1. Unscrew the mounting screw 
.
2. Press push-button
until the valve
is completely closed (VFU 2
completely open) and the direction 
indicator 
stops.
Observe stroke indicator, it must move to 
position 
.
3. Turn the screw
until the cam
with line of the selected stroke
is
aligned with the actuator of the end 
switch.
Note:
Select the valve stroke from the table below.
Type
DN 15 20 25 32 40 50 65 80
VFG 2
VFG 21
VFG 25
mm
6
8
12
18
AFQM
-
12 18
AFQM 6
-
8 12
-
VFU 2
8
10
14
20
Note:
Only special actuator types are equipped
with end switches, see rating plate.
The adjustment of the end switches must
be done after the stroke has been set. 
a. Unscrew the »Allen key« screw 
b. Adjust the stroke of the electrical
actuator regarding to chapter: 
”Mechanical stroke setting”
Adjusting the Additional 
End Switch
10
1. Press push-button
until the valve
is completely closed (VFU 2
completely open) and the direction 
indicator 
stops.
Observe stroke indicator, it must move to 
position 
.
9