Installation Guide

AMV 410, AMV 413

Danfoss Heating

VI.AA.U4.7S

DEN-SMT/SI

ENGLISH

Safety Notes

Prior to assembly and commissioning
to avoid injury of persons and damages
of the devices, it is absolutely necessary
to carefully read and observe these
instructions.

Necessary assembly, start-up, and
maintenance work must be performed
only by qualified, trained and authorized
personnel.

Prior to assembly and maintenance work
on the controller, the system must be:
- depressurized,
- cooled down,
- emptied and
- cleaned.

Please comply with the instructions of the

system manufacturer or system operator.

Definition of Application

The electrical actuator is used in
connection with the following valves:
VFG 2(21), VFG 25, VFU 2, VFGS 2, AFQM
and AFQM 6.

Fields of application are the temperature
control of water, water-glycol mixtures
and steam for heating, district heating and
cooling systems.

Safety Return Function and
Effective Direction

2

Safety function and effective direction of
stem: valid only for AMV 413.

Mounting

Permissible Installation Positions

1

Valve Installation

3

1. Install strainer in front of valve.
2. Rinse system before installing valve.
3. Observe flow direction

on the valve

body.

Flanges

in the pipeline system must be

in parallel direction, the sealing surfaces

must be clean and undamaged.

4. Install valve.

Actuator and Valve Installation

4

The actuator must only be mounted with
the stem retracted

.

Stroke indicator

must be in position

.

On delivery the stem is retracted with a
screwed-in mounting screw

.

If this is not the case, then:
1. Carry out the electrical connection, see

next section.

2. Press push-button

and completely

retract the stem

.

3. Screw in mounting screw

up to its

stop.

4. Place actuator on the valve and align.
5. Tighten union nut

torque 100 Nm.

6.

It is absolutely necessary to unscrew
the mounting screw

, otherwise, the

actuator is out of function.

7. If the actuator is installed in a downward

hanging position

, remove label

.

Insulation

5

Dimensions

6

Flanges: connection dimensions acc. to
EN 1092-2, seal form C.

Electrical Connection

7

HIGH VOLTAGE !

Danger of injury and life in case of

improper handling.

Switch off power supply prior to
connecting lines.

The electrical connection must only be
performed by an expert electrician.

Procedure
1. Unscrew cap nut

and remove cover

.

2. Connect lines in accordance with

connection diagram.

3. Prior to remounting the cover, carry out

settings at the actuator, see part

8

.

Electrical Connection Diagram

8

Connection for:
STB - Safety Temperature Limiter

STW - Safety Temperature Monitor

SDB - Safety Pressure Limiter

Prior to connection, it is absolutely necessary

to remove the jumper (terminals 4-7).

Only types AMV 413 with safety return

function.

Mechanical Stroke Setting

9

The stroke of the electrical actuator must
be adjusted to the valve stroke.
1. Unscrew the mounting screw

.

2. Press push-button

until the valve

is completely closed (VFU 2

completely open) and the direction
indicator

stops.

Observe stroke indicator, it must move to
position

.

3. Turn the screw

until the cam

with line of the selected stroke

is

aligned with the actuator of the end
switch.

Note:

Select the valve stroke from the table below.

Type

DN 15 20 25 32 40 50 65 80

VFG 2

VFG 21

VFG 25

mm

6

8

12

18

AFQM

-

12 18

AFQM 6

-

8 12

-

VFU 2

8

10

14

20

Note:

Only special actuator types are equipped

with end switches, see rating plate.

The adjustment of the end switches must

be done after the stroke has been set.
a. Unscrew the »Allen key« screw

b. Adjust the stroke of the electrical

actuator regarding to chapter:
Mechanical stroke setting”

Adjusting the Additional
End Switch

10

1. Press push-button

until the valve

is completely closed (VFU 2

completely open) and the direction
indicator

stops.

Observe stroke indicator, it must move to
position

.

9