1

24 V

230 V

A

A

B

B

32 mm

3

2

4

73691180 DH-SMT/SI

VI.KU.N2.1J

© Danfoss 01/2008

2

safety Note

Prior to assembly and commissioning

to avoid injury of persons and damages

of the devices, it is absolutely necessary

to carefully read and observe these

instructions.
Necessary assembly, start-up, and

maintenance work must be performed

only by qualified, trained and authorized

personnel.
Prior to assembly and maintenance work

on the controller, the system must be:

- depressurized,

- cooled down,

- emptied and

- cleaned.

Please comply with the instructions of the

system manufacturer or system operator.

Mounting

1

The actuator should be mounted with the

valve stem in either horizontal position or

pointing upwards.

Wiring

2

Do not touch anything on the PCB!

Lethal voltage!
24 V

Grey

Stem down

Black

Common

Red

Stem up

230 V

Black

Stem down

Blue

Common

Brown

Stem up

Installation

3

1. Check the valve’s neck. The actuator

should be in stem up position (factory

setting). Ensure that the actuator is

mounted securely on the valve body.

2. Energise the actuator according to the

wiring diagram - see above.

3. The direction of stem movement can be

observed on the position indicator .

Manual override

4

Press and hold the button  (on the

bottom side of the actuator) during manual

override.
Remark:
A ”Click” sound after energizing the actuator

means that the gear wheel has jumped into

normal position.

ENglIsh