Xantrex Technology FREEDOM SW 3000 User Manual
Page 65

975-0545-01-01
51
Troubleshooting
Table 9
provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact
your dealer or Customer Service.
Table 9 Fault Messages
Fault
Number
Message
Fault Type
Cause
Solution
F0
Unit is too hot and has shut
down. See guide.
Automatic
FET1 Over Temperature
Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.
F2
Unit is too hot and has shut
down. See guide.
Automatic
FET2 Over Temperature
Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.
F3
Unit is too hot and has shut
down. See guide.
Automatic Transformer
Over
Temperature Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.
F4
Battery over-temp. Inv/Chg
has shut down. See guide.
Automatic
Battery Over Temperature
Shutdown
Clear the fault and attempt restart. Stop
charging, check battery voltage and
temperature. Check for excessive ambient
temperature and adequate ventilation in
the battery compartment.
F5
is too hot and has shut
down. See guide.
Automatic
Ambient Over Temperature
Shutdown
Clear the fault and attempt restart. Ensure
adequate ventilation around Freedom SW
3000. Reduce AC loads.