York PV9 User Manual
Page 3
036-21584-001 Rev. B (1004)
Unitary Products Group
3
NOTE: For high altitude conversion, an orifice change may also be required. See Form 035-14447-001 for application information.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
NOTES:
1. All filters must be high velocity cleanable type.
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
HIGH ALTITUDE PRESSURE SWITCH APPLICATION
Models
High Altitude Pressure Switch Kit
4,500 Ft to 10,000 Ft.
PV9A12N040UP11
1PS0506
PV9B12N060UP11
1PS0501
PV9B12N080UP11
1PS0502
PV9C16N080UP11
1PS0503
PV9C20N100UP11
1PS0505
PV9D20N120UP11
1PS0503
ELECTRICAL AND PERFORMANCE DATA
Models
Input
High/Low
Output
High/Low
Nominal
Airflow
AFUE
Air Temp.
Rise
Max. Outlet
Air Temp.
Blower
Blower
Size
Total Unit
Max.
Over-current
Protect
Min. Wire Size
(awg) @ 75 ft.
One Way
MBH
MBH
CFM
%
°F
°F
HP Amps
In.
Amps
PV9A12N040UP11
40/26
38/24
1200
94.0
35-65
165
1/2
7.7
11x8
9
20 14
PV9B12N060UP11
60/39 56/36 1200
93.2
40-70 170 1/2
7.7
11x8 9
20
14
PV9B12N080UP11
80/52 75/49 1200
92.5
45-75 175 1/2
7.7
11x8 9
20
14
PV9C16N080UP11
80/52 75/49 1600
92.8
45-75 175 3/4
9.6
11x10 12
20
14
PV9C20N100UP11
100/65 93/60 2000
92.8
45-75
175 1
12.8
11x11 14
20
12
PV9D20N120UP11
120/78 112/73 2000 93.2
40-70
170 1
12.8
11x11 14
20
12
FILTER SIZES
Models
CFM
Cabinet Size
Side Return Filter in. (cm)
Bottom Return Filter in. (cm)
PV9A12N040UP11
1200
A
16 x 25
14 x 25
PV9B12N060UP11
1200
B
16 x 25
16 x 25
PV9B12N080UP11
1200
B
16 x 25
16 x 25
PV9C16N080UP11
1600
C
16 x 25
20 x 25
PV9C20N100UP11
2000
C
16 x 25
20 x 25
PV9D20N120UP11
2000
D
(2) 16 x 25
22 x 25