Specifications, Continued) – York STYLE A YCWS User Manual

Page 6

background image

6

YORK INTERNATIONAL

override for servicing.
Print - Operating data or system fault shutdown history
for last six faults. Printouts through an RS-232 port via a
separate printer (by others).
Program -
• Low leaving liquid temperature cutout, 300 to 600

second anti-recycle timer, lag compressor start time
delay, and average motor current unload point. Liq-
uid temperature setpoint reset signal from YORK ISN
or building automation system (by others) via:

• Pulse width modulated (PWM) input for up to 40°F

(22°C) total reset as standard.

• Optional Building Automation System interface input

card for up to 20°F (11.1°C) reset using a: 4 to 20
mA, 0 to 10 Vdc input, or discrete reset input.

• NOTE: The Standard MicroPanel can be directly con-

nected to a YORK ISN Building Automation System

Specifications

(Continued)

via the standard onboard RS485 communication port.
This Option also provides open system compatibility
with other communications networks (BACnet™ &
LONMARK™ via interface through standard onboard
485 or 232 port and an external YorkTalk Translator.

• Additional functions (password protected) for program-

ming by a qualified service technician:

Cutouts for low suction pressure, high discharge
pressure, high oil temperature.

Refrigerant type.

High discharge pressure unload setpoint.

Compressor motor current percent limit.