DIRECT-VENT NATURAL GAS HEATER

THE COMFORT PRODUCTS PEOPLE

6" Minimum

Adjacent

Side
Wall

Ceiling

Finished Floor, Carpet, Tile, etc.

12"

Minimum

12" Minimum

Figure 1 - Mounting Clearances as Viewed
from Front of Furnace

The clearance between the cabinet and the
wall it passes through is 0 inches.

Provide the following minimum clearances
from furnace cabinet (portion of cabinet
extending into outside air, as viewed from
the rear of furnace) to obstructions:

Cabinet Back: 36 inches

Cabinet Sides: 6 inches

Cabinet Bottom: Must be high enough
off the ground to prevent snow, water,
leaves, or any other objects from block-
ing vents.

Minimum Clearances

Provide the following minimum clearances
from furnace front cover to combustibles
(as viewed from the front of furnace, see
Figure 1):

Below Front Cover: 6 inches
Above Front Cover: 12 inches
Adjoining Wall: 12 inches
Front: 8 feet

WARNING: Due to high tem-

peratures, never install the furnace:

• in an inside wall
• in a recreation vehicle
• in a window recessed in a thick

wall (creating an alcove)

• in an alcove
• behind a door or where an open

door would block normal air flow

• as a fireplace insert
• in high traffic areas
• near furniture or draperies
• in windy or drafty areas

CAUTION: If you install the

furnace in a home garage, locate
furnace where moving vehicle will
not hit it.

For convenience and efficiency, install furnace:

• where there is easy access for operation,

inspection, and service

• in a central location, near an electrical

outlet

• where there is adequate clearance around

vents outside

Before installing furnace, inspect the wall,
floor, and outside areas. Make sure there are
no pipes, wiring, or anything else that would
interfere with furnace installation. If you are
installing thermostat in a wall, make sure
there are no pipes or wiring in the hollow
wall above the furnace. The thermostat wires
will pass through this wall from the attic.

Mounting hardware needed to mount fur-
nace into wall is included with the furnace.
No venting material is needed. You must
furnish tools and all gas piping from the gas
source to the furnace inlet.

INSTALLATION

WARNING: A qualified ser-

vice person must install furnace.
Have service person inspect fur-
nace before use and at least an-
nually. Follow all local codes.

CHECK GAS TYPE

Use only natural gas. If your gas supply is
not natural gas, do not install furnace. Call
dealer where you bought furnace for proper
type furnace.

INSTALLATION ITEMS

Before installing furnace, make sure you
have all items below:

• electric drill

• drill bits

• Phillips screwdriver

• hammer

• pipe wrench

• stud locator or small finishing nails

• equipment shutoff valve (supplied)

• test gauge connection (see Figure 15,

page 10)

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• ground joint union

• sediment trap

• tee joint

LOCATING FURNACE

This furnace is designed to be mounted in a
wall that is 4 to 18 inches thick. You can also
mount furnace in a window.

WARNING: Do not install fur-

nace in interior wall of building. You
must install furnace in exterior wall
of building. Rear of furnace must
extend into open, outside air. This
lets poisonous exhaust gases ven-
tilate to the outdoors.

WARNING: Maintain the mini-

mum clearances shown in Figure
1. If you can, provide greater clear-
ances from floor, ceiling, and
joining wall.

WARNING: Turn off electrical

circuits that pass through the wall
where you are going to install the
furnace.

NOTICE: This furnace must be
electrically grounded. Follow all
local codes. In the absence of
local codes, follow the

National

Electric Code, ANS/NFPA 70
(U.S.) or Canadian Electrical Code
Part I-CSA C22.1 (Canada).