Connect water boiler piping – Weil-McLain 78 User Manual

Page 13

background image

General water piping information:

• System water supply and return piping should

be installed and piping connections attached to
boiler before erecting jacket or installing
controls.

• Do not pipe in through supply and out through

return. This creates reverse water flow through
boiler that must not be used.

• When three-way valves are used for

temperature modulation, install slow-opening
(minimum 10-minute) valves and boiler
mixing pump to minimize potential of boiler
thermal shock. See W-M Bulletin AE-8402.

Install piping:

Install piping as shown in Figure 12 below for
single boilers, page 14 for multiple boilers.

Improperly piped systems or undersized piping
can contribute to erratic boiler operation and
possible boiler or system damage.

1. Connect supply and return piping:

a. Size according to tables below.

1) For

unknown flow rates,

size piping

per Table below, using 20°F. temperature
rise through boiler.

* All piping sizes based on 20°F. temperature

rise through boiler.

2) For

known flow rates or higher flow

rate

through boiler, size piping per Table

below.

Flow at higher velocities than
shown in Table below for pipe
size can damage boiler, causing
substantial property damage.

b. Locate circulator in supply piping.
c. For return piping, use full diameter pipe for

10 times that diameter before making any
reduction. For example, a 4-inch return
should not be reduced any closer to boiler
return tapping than 40 inches.

d. Install system blow-off (drain) valve in

lowest part of return piping close to boiler.
ASME Size requirements are shown in
Table below.

Recommended Minimum Pipe Sizes

for Unknown Flow Rates*

Supply

Return

Boiler

Pipe Size

Pipe Size

Model

A

B

378

2"

2"

478

2-1/2"

2-1/2"

578-678

3"

3"

778-1278

4"

4"

• Installation • Start-Up • Maintenance • Parts

Connect Water Boiler Piping

5a

Part No. 550-141-705

13

Recommended Minimum Pipe Sizes

for Known Flow Rates

Water Supply

Return

Flow Rate

Pipe Size

Pipe Size

GPM

A

B

Up to 35

2"

2"

36 to 50

2-1/2"

2-1/2"

51 to 77

3"

3"

78 to 142

4"

4"

ASME Drain Valve Size

Boiler Model

Valve Size (in.)

378-478

3/4

578-1178

1

1278

1-1/4

Cold

water fill

Expansion

tank

System

supply

(front only)

System return

(front or rear)

Manual

isolation

valve

Manual

isolation

valve

Pressure

reducing

valve

(when used)

Figure 12 Water Boiler Piping

Check

valve

Water

meter