PLUS Line Instruction Manual Supplement

PLUS &

PLUS

WATER

HEATERS

WITH

GAS

-

FIRED

WATER

BOILERS

Notes

Tables 1 and 2

Table 1

Combined space heating/water heating applications (see Notes)

Install boiler-to-water heater piping

(continued)

2

1. First hour ratings in Tables 1 and 2 are based on:

• 115°F or 140°F domestic outlet water supply

temperature from water heater.

• 50°F domestic water inlet temperature.
• 190°F boiler water temperature leaving Ultra boiler.
• Circulator and pipe sizes as given in the Tables.

2. If the net Btu/hr rating of the boiler is close to the

space heating load (for combined systems) — or if
there is an unusually large demand for domestic
water — increased boiler capacity may be required.

Table 2

Dedicated water-heating only systems (using circulator supplied with boiler) (see Notes)

Figure 6

Pump curves for Taco circulators