Troubleshooting, Universal control systems — control supplement – Weil-McLain Boiler User Manual

Page 27

background image

Part Number 550-110-646/0607

Universal control systems — Control supplement

Troubleshooting

Burner access panel must be in posi-

tion during boiler operation to prevent

momentary flame rollout on ignition of

main flame. Severe personal injury or

substantial property damage will result.

Never jumper (bypass) any device ex-

cept for momentary testing as outlined

in Troubleshooting Charts. Substantial

property damage and/or severe personal

injury could occur.

Label all wires prior to disconnection

when servicing controls. Wiring errors

can cause improper and dangerous opera-

tion.

Verify proper operation after servicing. See

vent damper manufacturer’s instructions

packed with vent damper for additional

information. Failure to comply could

result in severe personal injury, death or

substantial property damage.

Before troubleshooting

1. Have a voltmeter that can check 10 VAC, VAC,

and a continuity tester.

. Check for 10 VAC (minimum 10 to maximum

1) to boiler.

. Make sure thermostat is calling for heat and contacts

(including appropriate zone controls) are closed.

Check for VAC between thermostat wire nuts and

ground.

In event of vent damper failure:

Effikal or Field Controls vent damper

If troubleshooting chart recommends replacing actuator and actuator is

not immediately available, damper blade can be fixed in an open position

to allow boiler operation.

Manually turning blade can cause actuator

damage

. Follow these instructions only in case of no heat or damper

actuator malfunction.
1. Move damper service switch to

Hold Damper Open

position. Apply call

for heat to boiler. Damper blade should then rotate to open position

and boiler will fire.

. If step 1 does not open damper, manually rotate damper blade to open

position using wrench or pliers on flat shaft between damper and actua-

tor. Boiler will fire. Verify that damper service switch is in Hold Damper

Open position (Figure 11).

.

Do not leave vent damper permanently in this position.

Replace actua-

tor immediately. If vent damper is left in open position, boiler will not

operate at published efficiencies.

Johnson Controls vent damper

If troubleshooting chart recommends replacing actuator and actuator is

not immediately available, damper blade can be fixed in an open position

to allow boiler operation. Follow these instructions only in case of no heat

or damper actuator malfunction. See Figure 11.
1. Turn off power to boiler.

Failure to turn off power to boiler can result in severe personal

injury, death or substantial property damage.

. Refer to vent damper manufacturer’s instructions for procedure to fix

vent damper in open position.

. Turn on power to boiler.
. Using wrench or pliers on flat shaft section, manually rotate damper

blade until green light turns on. Boiler will fire (Figure 11).

.

Do not leave vent damper permanently in this position

. Replace

actuator immediately. If vent damper is left in open position, boiler will

not operate at published efficiencies.

Figure 11

Manually opening vent damper