beautypg.com

Waterford Appliances LEPRECHAUN 90 O.S.A User Manual

Page 9

background image

between the outer wall of chimney section
and shall be 12” (305mm). Chimney
section concentric with and spaced 1”
(25mm) away from connector by means of
sheet steel support plates on both ends of
chimney section. Opening shall be covered
and chimney section supported on both
sides with sheet steel supports of min. 24
gauge thickness.

Supports should be securely fastened to wall sur-
faces on all sides and shall be sized to fit and hold
chimney section. Fasteners used to secure chimney
sections should not penetrate chimney flue liner.

other listed chimney connector from the appliances
flue outlet up through the fireplace damper and
smoke chamber, terminating at the first flue tile, or
by installing a stainless steel or other listed relining
system from the flue outlet up the entire length of the
chimney, where necessary.

In Canada when connecting to a masonry fire place
the steel chimney connector must terminate at the
top of the chimney or flue liner.

9

MASONRY FIRE PLACE

The stove maybe installed on the hearth extension
of a masonry fireplace. In Canada a continuous
liner must be provided from the flue collar of the
stove to the top of the chimney. In the USA a con-
tinuous chimney flue is required. A minimum clear-
ance of 25” (635mm) is required to combustible
mantle and a minimum clearance of 14” (355mm) to
side trim, which extends less than 2” (50mm) from
the face of the fireplace. (See Section under
Minimum Clearances to Combustibles).

Before the installation the entire fireplace system
should be inspected for condition and code compli-
ance prior to connecting to the fireplace chimney.
Older fireplaces and chimneys may not have been
constructed to current-day codes.

The fireplace and chimney should be in, or brought
up to, acceptable conditions and proper clearances
should be met before connecting to the fireplace
chimney.

The size of the flue must be considered. If the fire-
place chimney is too large, a relining system may be
installed using an approved relining system.

Connection to a masonry chimney may be done by
breaching into the chimney from the front of the fire-
place, no less than 8” (200mm) above the bottom of
the first flue tile, by installing a stainless steel or

Stainless Steel
Chimney Connector

Insulated non-combustible
throat seal

Flue Liner

VENTILATION & COMBUSTION AIR
REQUIREMENTS

Ventilation and an adequate air supply is necessary
to supply combustion air to the appliance. Refer to
your local Authority for current requirements in your
jurisdiction.

Outside combustion air may be required if:

The solid-fuel-fired appliance does not draw
steadily, smoke rollout occurs, fuels burns
poorly, or back drafts occur whether or not
there is combustion present.

Minimum chimney clearance
to sheet steel supports and
combustibles 2” (50mm)

Chimney
Section

Minimum clearances 2” (50mm)

1” (25mm) air
space to
chimney length

Chimney length

Air Space 2”
(50mm)

FIGURE D