Additional connection for +15 vdc encoder, Step 10: set speed reference to 20 – Vector 6SE70 VC User Manual
Page 23

Version 1.0 March 1, 2000
Page 23
Additional Connection for +15 Vdc Encoder.
Step 10: Set Speed Reference to 20%.
Step 11: Provide Start command. Note that if Signal A and Signal B are
reversed, the motor will accelerate rapidly.
Step 12: Connect the motor to the load, unless the plan is to change to
Vector Control.
Standard Commissioning for a Volts/Hz
controlled motor with feedback is
complete, after adjusting only 24
parameters.