Chimney connection – United States Stove Company HOTBLAST 1200G User Manual
Page 8
8
•DRAWINGS FOR ILLUSTRATION PURPOSES ONLY•
LISTED FACTORY BUILT CHIMNEY
Carefully follow chimney manufacturer's instructions. Use only a Listed Residential Type or Building Heating
Appliance Chimney. If your chimney starts at the ceiling (Fig. 5), you will need enough 6" pipe to reach the ceiling.
The top of the chimney must be at least 3 feet above the roof and be at least 2 feet higher than any point of the
roof within 10 feet (Fig. 5).
FIG. 5
MASONRY CHIMNEY
Before using an existing masonry chimney, clean the chimney and inspect the flue liner to be sure it is safe to use.
Make repairs before attaching the furnace. See Page 4, item 5. Look at Fig. 4. The connector pipe and fittings
you will need to connect directly to a masonry chimney are shown.
The chimney connection should be as short as possible. If the connector pipe must go through a combustible wall
before entering the masonry chimney, consult a qualified mason or chimney dealer. The installation must conform
to local fire codes, and N.F.P.A. 211.
DO NOT CONNECT THIS FURNACE TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
The chimney used for a furnace must not be used to ventilate the cellar or basement. If there is a cleanout opening
at the base of the chimney, close it tightly.
FIG. 4
CHIMNEY CONNECTION