Performance data – Trane XV 90 User Manual

Page 10

background image

10

Pub. No. 22-1682-05-0802 (EN)

Performance
Data

TUY120R9V5V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR

UNIT SIZE

(TONS)

AIRFLOW

SETTING

(See Notes)

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 1

SW 2

SW 3

SW 4

0.1

0.3

0.5

0.7

0.9

3.5

LOW

(350 CFM/TON)

OFF

ON

OFF

ON

CFM

WATTS

1210

220

1210

270

1220

325

1230

400

1230

445

NORMAL

(400 CFM/TON)

OFF

ON

OFF

OFF

CFM

WATTS

1400

305

1440

390

1450

465

1450

510

1410

560

HIGH

(450 CFM/TON)

OFF

ON

ON

OFF

CFM

WATTS

1590

425

1600

520

1610

600

1600

645

1380

575

4.0

LOW

(350 CFM/TON)

ON

OFF

OFF

ON

CFM

WATTS

1390

305

1400

375

1430

445

1440

515

1420

565

NORMAL

(400 CFM/TON)

ON

OFF

OFF

OFF

CFM

WATTS

1620

420

1650

530

1670

595

1640

660

1480

600

HIGH

(450 CFM/TON)

ON

OFF

ON

OFF

CFM

WATTS

1840

600

1830

690

1820

765

1670

700

1490

620

5

LOW

(350 CFM/TON)

OFF

OFF

OFF

ON

CFM

WATTS

1800

570

1780

630

1780

705

1700

695

1530

615

NORMAL

(400 CFM/TON)

OFF

OFF

OFF

OFF

CFM

WATTS

2050

845

2010

875

1860

805

1710

735

1530

655

HIGH

(450 CFM/TON)

OFF

OFF

ON

OFF

CFM

WATTS

2160

995

2040

935

1920

875

1780

805

1620

730

NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

TUY120R9V5V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity =
2nd Stage Capacity =

74,000

112,000

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 7

SW 8

0.1

0.3

0.5

0.7

0.9

HEATING

1ST

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

1090

62

165

1120

60

225

1080

63

270

1070

63

310

1010

67

380

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1210

56

220

1200

56

280

1200

56

330

1180

57

395

1160

58

455

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

1340

50

295

1360

50

350

1370

49

425

1380

49

495

1330

51

535

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1430

47

390

1570

43

490

1580

43

565

1570

43

625

1390

49

565

HEATING

2ND

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

1660

63

485

1690

62

590

1680

62

640

1640

64

675

1460

72

600

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1870

56

675

1870

56

745

1810

58

770

1680

62

715

1490

70

625

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

2060

51

880

1990

53

890

1850

57

810

1710

61

750

1530

68

665

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

2200

48

1030

2090

50

965

1940

54

895

1790

58

830

1640

64

750

NOTES:
** Factory setting