1. Introduction

2. Installation and Setup

1.1 Product Features

2.1 System Requirements

2.2 Communications Setup

1.2 Package Contents

The RELAYIOCARD is a programmable UPS management device featuring:

6 programmable relay output contacts

Configurable normal open or normal close for each relay contact

Configurable UPS shutdown delay time

Configurable input signal to shutdown UPS or test battery

The RELAYIOCARD allows you to:

Monitor UPS status and events

Perform remote system shutdowns and battery tests

The RELAYIOCARD supports all Tripp Lite SmartOnline™ UPS Systems and select SmartPro™ UPS Systems, including SMART1050SLT,
SMART1500SLT, SMART2200RMXL2U, SMX1050SLT, SMX1500SLT, SMART3000SLT, SMART2200SLT, SM2200RMNAFTA, SMART2600RM2U,
SMART3000RM2U, SMART1500CRMXL, SMART1500SLTXL, SMART750XLa, SMX3000XLRT2U and SMX2200XLRT2U. Supported systems must
run a UPS protocol of 3008 or above.

To determine your UPS protocol:

Open Tripp Lite PowerAlert software.

1.

Click on the “Misc” button on the main screen of the PowerAlert console.

2.

View the protocol variable.

3.

Connect Tx to pin2, Rx to pin 3 and GND-C to pin5 of RS-232 DBP port.

1.

In the Windows environment, launch the Hyper Terminal program, then open the specified COM port.

2.

Set the following properties – Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.

3.

This Package Contains:

RELAYIOCARD

Configuration Cable

Faceplates

Owner’s Manual

PROGRAMMABLE RELAY I/O CARD

USER MANUAL

PRESENTATION

FEATURES

This relay I/O card is an UPS management

product with 6 relay output contacts for monitoring

the status and 1 input contact as a shutdown UPS

or a battery test command.

Features:
z

Monitor UPS events.

z

6 programmable relay output contacts.

z

Configurable normal open or normal close for

each relay contact.

z

Configurable UPS shutdown delay time.

z

Configurable input signal as shutdown UPS or

battery test.

z

Has the ability to protect up to 6 computers

unattended shutdown gracefully.

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION

Size

130 x 60 mm

Weight

200 g

Operating Temperature 0 ~ 40q C

Operating Humidity

10 ~ 80 %

Power Input

8 ~ 20V DC

Power Consumption

1.2 Watts

OUTPUT CONTACT RATING

Maximum

DC Voltage DC Current

Relay

R1~R6

24 V

1A

INPUT RATING

Maximum

DC Voltage DC Current

Input

24 V

10 mA

APPLICATION EXAMPLE

In this case we’ll use the default settings, please

set SW1 and SW2 to the OFF position. Apply

12VDC to

Common contact and connect the

lamps to

R1~R6 terminals. Install a push button

from the Common contact to the input terminal.

Press the button for at least 3 seconds to

shutdown the UPS remotely.

Common

GND-R

R1

R2

R3

R4

R5

Input

+12V

Summary Alarm

Power Fail

Battery Low

On Bypass

Overload

Shutdown UPS

R6

Over Temperature

INTERNAL CIRCUIT

R1

R2

R3

R4

R5

Common

GND-R

Input

+5V

CPU Pin

R6

OUTLINE

GND-R

Common

R1

R2

R3

R4

R5

R6

Input

Tx

Rx

GND-C

SW1

SW2

I/O PINOUT

GND-R: Ground for relays

Common: 12~24VDC

Default Alarm Event

R1

Summary Alarm

R2

Power Fail

R3

Battery Low

R4

On Bypass

R5

Overload

R6

Over Temperature

Input: Remote shutdown or battery test

Tx: Transmit to PC, connect to sub9-pin2

Rx: Receive from PC, connect to sub9-pin3

GND-C: Ground for configuration Tx and Rx pins

OFF (Default)

ON

SW1 Normal open

for default settings

Normal close

for default settings

SW2 Default settings

Customized settings

PROGRAMMABLE CONTACTS

COMMUNICATION SETUP

1. Connect

Tx to pin2, Rx to pin3 and GND-C to

pin5 of PC RS232 port.

2. In the Windows environment, launch the

Hyper- Terminal program then open the

specified COM port.

3. Set the following properties:

Baud rate:

2400, Data Bits: 8, Parity: None

Stop Bit:

1, Flow Control: None

CONFIGURATION

1. Press to get the main menu of the

programmable relay card.


_8365HOD\&DUG_

)LUPZDUH9HUVLRQ5HOD\&DUG9
>@&XVWRPL]H2XWSXW5HOD\
>@&RQILJXUH,QSXW6LJQDO
>@&XVWRPL]H1RUPDO2SHQRU1RUPDO&ORVH
>@4XLW

3OHDVH(QWHU

2. Press ‘1’ to configure the alarm event for

R1~R6.

Contacts

R1~R6 can be configured for

different power events.


_&XVWRPL]H2XWSXW5HOD\_

5HOD\6HOHFWHG(YHQW
>@5HOD\6XPPDU\$ODUP
>@5HOD\3RZHU)DLO
>@5HOD\%DWWHU\/RZ
>@5HOD\2Q%\SDVV
>@5HOD\2YHUORDG
>@5HOD\2YHU7HPSHUDWXUH
>@%DFN7R3UHYLRXV0HQX

3OHDVH(QWHU

Once the configuration is complete

SW2

MUST be switched to the ON position to apply

the new settings, switch

SW2 back to the OFF

position to reset to the default settings.

3. Press ‘2’ to configure the

Input signal.


_&RQILJXUH,QSXW6LJQDO_

>@$FWDV6KXWGRZQRU7HVW6KXWGRZQ
>@,QSXW6LJQDO&RQILUP6HFRQGV
>@'HOD\%HIRUH6KXWGRZQ6HFRQGV
>@%DFN7R3UHYLRXV0HQX

3OHDVH(QWHU

In this menu, the input signal can be redefined

as shutdown UPS or battery test signal.

Meanwhile, the UPS shutdown delay time is

also adjustable to a maximum of 9999

seconds.

4. Press ‘3’ to configure the normal open or

normal close for each relay.


_&XVWRPL]H2XWSXW5HOD\_

5HOD\6HOHFWHG(YHQW
>@5HOD\1RUPDO&ORVH
>@5HOD\ 1RUPDO2SHQ
>@5HOD\ 1RUPDO&ORVH
>@5HOD\1RUPDO2SHQ
>@5HOD\1RUPDO&ORVH
>@5HOD\1RUPDO2SHQ
>@%DFN7R3UHYLRXV0HQX

3OHDVH(QWHU

Once the configuration is complete

SW2

MUST be switched to the ON position to apply

the new settings. Switch

SW2 back to the

OFF position to reset to the default settings.

5. Press ‘0’ to quit this configuration session.

The system would prompt you to save or not.

Press ‘Y’ to save your settings, ‘N’ to ignore.

POWER OPTION IN WIN 2000/XP

This relay card has the ability to provide UPS

signals for Windows NT4/2000/XP/2003. First

connect the RS232 port on the PC to the relay

card as shown:

Then open the power option from control panel

and click on the UPS tab to setup the signals

polarity, select

Positive for Power Fail, Low

Battery and UPS

Shutdown.

Since the

R1~R6

contacts are

programmable,

the output

contacts can be

configured for 3

computers with 2

signals (power fail

and low battery) or

6 computers with

one signal (power

fail or low battery).

Note: All of the computers must have the same

earth ground potential. Connect all of the

computers input power to the same UPS.

Common

GND-R

R1

R2

R3

R4

R5

Input

Power Fail

R6

Battery Low

RTS pin7

GND pin5

CTS pin8

DCD pin1

DTR pin4

Shutdown UPS