Rs485 – Telenetics MIU Dial or Leased Line modem with RS-485 User Manual
Page 15
CIU Installation, Operation & Diagnostics
Edition: June 17, 2003
Page C-1
SB-1
Closed(ON) DC Terminated
SB-2
Closed (ON) Line Termination
SB-3 & -4 Open (OFF) 4- wire
SA-1 Open (OFF) RTS follows CTS no delay
SA-2
Open (OFF)
SA-3
Closed (ON) RTS (always ON by MIU internal J7 (1/2)
setting) enables TxEN)
SA-4
Open (OFF) TxD will not disable RxD
MIU S3 (external)
SW-1 Closed (ON) MIU is configured for RS485 Module (RS485 RxD
(Output) to Modem TxD (input))
SW-2, -3 & -4 Open (OFF)
SA2 & SA3 can be configures for TxD enable TxEn signal if there
are several master locations in the network.
SA2 is Closed (ON) TxD (transmit data) enables TX (Driver Output
Enable)
+ 5ms
SA3 is Open (OFF) TxD will not disable RxD
MIUXXXX/485 Final Connection
Ensure that MIUXXXX/485 J7 (internal jumper) 1/2 is connected
APPENDIX C.
CONNECTOR DIAGOSTICS
RS485
CONNECTION FAILURE