Miuxxx/485 dip switch setup – Telenetics MIU Dial or Leased Line modem with RS-485 User Manual
Page 10
CIU Installation, Operation & Diagnostics
Edition: June 17, 2003
SHEET TWO
B
Point-to-Point, 4-Wire: Set Switches B-3 & B-4 DOWN(OFF)
Point-to-Point, 2-Wire: Set Switches B-3 & B-4 UP(ON)
Line Terminate DC : Set Switches B-1 & B-2 UP(ON)
Line Terminate AC : set Switches B-2 UP(ON)
For LoopBack Test mode : Set Switches B-3 & B-4 UP(ON)
Set Switch A-4 DOWN(OFF)
Multi-drop (Host), 4-Wire: Set Switches B-3 & B-4 DOWN
Multi-drop (Host), 2-Wire: Set Switches B-3 & B-4 UP
Multi-drop (Slave), 4-Wire: Set Switches B-3 & B-4 DOWN
Multi-drop (Slave), 2-Wire: Set Switches B-3 & B-4 UP
Line Terminate
: Set Switches B-2 & B-1DOWN (OFF) for
all Slaves except UP(ON) on unit furthest
from the Host
Switch A-1:
RTS/CTS Delay: UP = 0 sec; DOWN = 7ms
Switch A-2:
DOWN = TXD enables TX +5ms Select only A-2 or
Switch A-3:
DOWN = RTS enables TX A-3
Switch A-4:
UP(ON) = TX clamps RXD off (ON) in 2-Wire (half duplex) mode
A
B
4 3 2 1 4 3 2 1
A
B
4 3 2 1 4 3 2 1
A
4 3 2 1 4 3 2 1
Earth/Digital Ground (Jump pins if req’d) *
LED 1...
♦
Blinking = POWER ON
♦
Steady = MODEM CONNECTED (CD)
RJ11 Telco Port *
Power Connector
LED 1 *
RS232 Data Port (DB9 female)
for modem configuration only.
RS485
Connection
TX+ TX- RX+ RX-
(* Not on MIU232/485 Converter)
3 & 4 always UP.
1 UP, 2 DOWN when using DB9
for modem configuration.
1 DOWN, 2 UP ~ Modem
connected to RS485. Do not
connect data to DB9
B A
MIUXXX/485 DIP SWITCH SETUP