beautypg.com

Trion Air Boss ATS User Manual

Page 5

background image

5

Efficiency-Curves 1, 2 and 3

1. Overall DOP (Dioctylphthalate) efficiency

using 10 Stage Cascade Impactor

2. ASHRAE Standard 52 Dust Spot Test

Method Atmospheric Air

3. 0.3 Micron DOP efficiency using 10

Stage Cascade Impactor

Pressure Drop Across Unit-Curves 4, 5 and 6

4. Cell with 40% open perforated plate, front and rear

5. Cell with 1” metal mesh filter, front and rear

6. Cell only

AIR VELOCITY FEET PER MINUTE

Principle of Operation

Dirty Air

Pre-Filter

Ionizer

Collector

Clean Air

Electronic Air Cleaning

Media Module (optional)

The flexibility of the media module provides an efficient means

for high efficiency filtration, as a prefilter or afterfilter, depend-

ing on your requirement. This section is designed to house a

variety of mechanical filters that may be required in your appli-

cation. The housing allows for various filter combinations that

are tailored to your specific needs, such as HEPAs, 95% bags,

mini-pleated cartridges or other media. The heavy-gauge

access housings are supplied with industrial-grade hardware.

Adsorber Module (optional)

Unlike particulate filters, odors in the form of undesirable gases

and vapors are most commonly removed from the air stream by

the process of adsorption that is enhanced by multi-faceted

porous surfaces of certain materials. Filter trays of activated carbon

or optional potassium permanganate pellets effectively facil-

itate the adsorption of these odors and gaseous contaminants.

Standard Blower Module Package

The energy-efficient, backward-inclined blower, powered by a

TEFC motor, is designed for horizontal air flow and mates with

the air purification system to provide a uniform distribution of

air. The bolted rear panel provides service access. Air discharge

screen and rain guard are available as options. The blower

wheel is steel, backward-inclined, all-welded construction.

Optional UpBlast Blower

The NFPA 96 UpBlast fan is designed to mate with the air

purification system and provide uniform air distribution. It is a

centrifugal upblast exhaust fan, with drain, in compliance with

UL 762 for kitchen exhaust applications containing grease-laden

air. The blower wheel is steel, backward inclined, all welded

construction.