TS 870 TRANSFER SWITCH

PM062 REV 5 08/05/05

4

Thomson Technology

To change the transfer switch voltage, refer to “

INSTRUCTIONS TO CHANGE SYSTEM

VOLTAGE ON TS870 SERIES TRANSFER SWITCHES WITH TSC 80

CONTROLLER”

(attached as “

Appendix B). Contact Thomson Technology for further

information as may be required.

3.4.

SYSTEM PHASING-HIGH LEG DELTA SYSTEMS

For systems using high leg delta 240V 3 phase 4 wire systems, connection of supply

conductors must have the correct phasing as shown below.

WARNING

Failure to match correct system

phasing will result in serious damage

to the TSC 80 controller.

208V

B

(Orange)

(High Leg)

C

(Yellow)

A

(Red)

N

(W hite)

PH A

(UA)

Autom atic Transfer

Switch (Utility Supply)

PH B

(UB)

PH C

(UC)

Neural

(N)

120V

120V

240V

240V

Where transfer switches are supplied without power isolation transformers (PT1 &

PT2) for ATS control logic it is essential that the orientation of phase conductors of